SIL 4519 Z
Single-phase Silensys outdoor condensing unit SIL 4519 Z for high-temperature duty, supplied ready for outdoor installation, 4912 W, R-404a or R-507.
- Dimensions
- -
Single-phase Silensys outdoor condensing unit SIL 4519 Z for high-temperature duty, supplied ready for outdoor installation, 4912 W, R-404a or R-507.
The Silensys SIL 4519 Z outdoor condensing unit is factory-ready and built for outdoor conditions, which shortens installation time. It serves high-temperature refrigeration (HBP −15…+10 °C) with R-404a or R-507 and runs on a single-phase 220–240 V / 50 Hz supply.
It comes with a receiver, sight glass, liquid-line filter drier, crankcase heater, HBP/LBP dual pressure switch, fan-speed controller and contactor. The electrical parts are pre-wired to the internal control panel; the housing locks, a main switch is fitted and brackets allow vertical or horizontal mounting.
A dual pressure switch with manual reset and a receiver with safety relief valve are available as options. To EN13215 (20 °C superheat, 3 K subcooling) the unit gives 4912 W of refrigerating capacity and draws 2174 W. Airflow is 3500 m³/h; the receiver holds 2.35 l.
It draws 10.0 A in operation and 12.6 A at most. Sound power 69 dBA; noise level 38 dBA at 10 m and 44 dBA at 5 m. Pipe connections are brazed, 5/8″ (16 mm) on the suction line and 3/8″ (10 mm) on the liquid line.
If you would rather not fit it yourself, our own service team can do the job as part of cold room repair.
We can confirm price and availability and help you choose a suitable model.