Book a service
About this product

Description

The Silensys SIL 4540 Z_3P is a three-phase outdoor condensing unit prepared at the factory for outdoor installation. It is designed for high-temperature refrigeration (HBP −15…+10 °C) with R-404a or R-507, in settings such as supermarkets, warehouses, butchers, fish shops and industry.

The package includes a 3.9-litre receiver, sight glass, liquid filter drier, crankcase heater, HBP/LBP dual pressure switch, fan-speed controller and contactor, with the electrics wired to an internal panel. A lockable housing, main switch and brackets for vertical or horizontal mounting are also part of the equipment.

A manual-reset dual pressure switch and a receiver with relief valve can be added as options. Refrigerating capacity to EN13215 is 5775 W at −10 °C evaporating (20 °C superheat, 3 K subcooling), with a power input of 4107 W. Running current 8.4 A, maximum 9.6 A, on 400 V / 50 Hz.

Airflow 3500 m³/h, sound power 70 dBA, noise level 39/45 dBA at 10/5 m. Connections 7/8″ (22 mm) and 1/2″ (12 mm).

Technical data

Specifications

Type
Outdoor condensing unit
Manufacturer
Tecumseh Europe
Model name
SIL 4540 Z_3P
Suction pressure
High suction pressure HBP -15°C..+10°C
Refrigerant
R-404a and R-507
Power consumption; W
4107
Refrigerating capacity to EN13215; W
5775; refrigeration capacity stated at an evaporating temperature of -10°C.
Refrigerating capacity note
Standard EN13215: refrigeration capacity is stated at suction gas superheat 20°C and liquid refrigerant subcooling 3K. Capacity is stated for a 1-phase unit. Data may differ for a 3-phase unit.
Sound power level; dBA
70
Noise level at 10 m / 5 m; dBA
39 / 45
Noise level note
Noise level is stated at maximum fan speed in free-field outdoor conditions according to EN13215: evaporating temperature +5°C, suction gas superheat 20°C, liquid refrigerant subcooling 3K and ambient air temperature +32°C. Tecumseh Europe uses the EN ISO 3743-1 noise measurement standard to bring published noise data as close as possible to on-site conditions.
Airflow; m³/h
3500
Refrigerant receiver capacity; L
3,9
Rated running current; A / maximum running current; A
8,4 / 9,6
Suction line diameter
7/8" (22 mm)
Liquid refrigerant line diameter
1/2" (12 mm)
Pipe connections
Brazed connections
External dimensions: length / width / height; mm
-
Gross and net weight; kg
-
Standard equipment
Refrigerant receiver, liquid refrigerant sight glass, liquid-line filter drier, crankcase heater, HBP/LBP dual pressure switch, fan-speed controller and compressor contactor. Internal electrical components pre-wired to the control panel. Lockable housing, main switch and mounting brackets for vertical or horizontal installation. Fan-speed control, aerodynamically shaped fan blades and sound insulation in the compressor compartment help reduce noise while supporting airflow.
Optional accessories
HBP / LBP dual pressure switch with manual reset; refrigerant receiver with a safety relief valve.
Voltage
3-400V-50Hz
Warranty
12 months