Book a service
About this product

Description

Ready for outdoor installation, the SIL 2464 Z belongs to Tecumseh Europe's Silensys range and is intended for low-temperature refrigeration in the LBP range of −40…−10 °C. It works with R-404a or R-507 on a single-phase 220–240 V / 50 Hz supply. The unit contains a receiver, sight glass, filter drier, crankcase heater, HBP/LBP dual pressure switch, fan-speed controller and contactor.

The electrics are pre-wired to the internal panel of the lockable housing, which also holds the main switch; brackets allow upright or horizontal mounting. Speed control, aerodynamic fan blades and compressor-compartment insulation make for quieter running. Refrigerating capacity to EN13215 is 956 W with a power input of 880 W, at 20 °C superheat and 3 K subcooling.

Current draw is 4.1 A rated and 7.9 A maximum. Airflow 1600 m³/h; receiver 1.5 l. Sound power 63 dBA; noise level 32 dBA at 10 m and 38 dBA at 5 m.

Brazed connections 1/2″ (12 mm) and 3/8″ (10 mm).

If you would rather not fit it yourself, our own service team can do the job as part of cold room repair.

Technical data

Specifications

Type
Outdoor condensing unit
Manufacturer
Tecumseh Europe
Model name
SIL 2464 Z
Suction pressure
Low suction pressure LBP -40°C..-10°C
Refrigerant
R-404a and R-507
Power consumption; W
880
Refrigerating capacity to EN13215; W
956
Refrigerating capacity note
Standard EN13215: refrigeration capacity is stated at suction gas superheat 20°C and liquid refrigerant subcooling 3K. Capacity is stated for a 1-phase unit. Data may differ for a 3-phase unit.
Sound power level; dBA
63
Noise level at 10 m / 5 m; dBA
32 / 38
Noise level note
Noise level is stated at maximum fan speed in free-field outdoor conditions according to EN13215: evaporating temperature -35°C, suction gas superheat 20°C, liquid refrigerant subcooling 3K and ambient air temperature +32°C. Tecumseh Europe uses the EN ISO 3743-1 noise measurement standard to bring published noise data as close as possible to on-site conditions.
Airflow; m³/h
1600
Refrigerant receiver capacity; L
1,5
Rated running current; A / maximum running current; A
4,1 / 7,9
Suction line diameter
1/2" (12 mm)
Liquid refrigerant line diameter
3/8" (10 mm)
Pipe connections
Brazed connections
External dimensions: length / width / height; mm
-
Gross and net weight; kg
-
Standard equipment
Refrigerant receiver, liquid refrigerant sight glass, liquid-line filter drier, crankcase heater, HBP/LBP dual pressure switch, fan-speed controller and compressor contactor. Internal electrical components pre-wired to the control panel. Lockable housing, main switch and mounting brackets for vertical or horizontal installation. Fan-speed control, aerodynamically shaped fan blades and sound insulation in the compressor compartment help reduce noise while supporting airflow.
Optional accessories
HBP / LBP dual pressure switch with manual reset; refrigerant receiver with a safety relief valve.
Voltage
1-220V/240V-50Hz
Warranty
12 months