SIL 2464 Z
Single-phase outdoor condensing unit SIL 2464 Z for low-temperature refrigeration at LBP −40…−10 °C, 956 W, Silensys range, R-404a or R-507.
- Dimensions
- -
Single-phase outdoor condensing unit SIL 2464 Z for low-temperature refrigeration at LBP −40…−10 °C, 956 W, Silensys range, R-404a or R-507.
Ready for outdoor installation, the SIL 2464 Z belongs to Tecumseh Europe's Silensys range and is intended for low-temperature refrigeration in the LBP range of −40…−10 °C. It works with R-404a or R-507 on a single-phase 220–240 V / 50 Hz supply. The unit contains a receiver, sight glass, filter drier, crankcase heater, HBP/LBP dual pressure switch, fan-speed controller and contactor.
The electrics are pre-wired to the internal panel of the lockable housing, which also holds the main switch; brackets allow upright or horizontal mounting. Speed control, aerodynamic fan blades and compressor-compartment insulation make for quieter running. Refrigerating capacity to EN13215 is 956 W with a power input of 880 W, at 20 °C superheat and 3 K subcooling.
Current draw is 4.1 A rated and 7.9 A maximum. Airflow 1600 m³/h; receiver 1.5 l. Sound power 63 dBA; noise level 32 dBA at 10 m and 38 dBA at 5 m.
Brazed connections 1/2″ (12 mm) and 3/8″ (10 mm).
If you would rather not fit it yourself, our own service team can do the job as part of cold room repair.
We can confirm price and availability and help you choose a suitable model.